Search
All Categories
    Menu Close

    C-Tec CFP Relay output card (reset, fault, aux & remote relay outputs)

    C-TEC

    CFP Relay output card (reset, fault, aux & remote relay outputs)

    SKU: XN01-CFP762
    SKU: XN01-CFP762
    Availability: In stock
    Branch Stock
    CorkIn Stock
    DublinIn Stock

    Log in Here - for Your Trade Prices

    Compatibility
    Application
    An optional system expansion device for use with CFP Standard 2-8 Zone Fire Panels or CFP AlarmSense 2-8 Zone Fire Panels
    Operation
    Relay Outputs
    Provides four panel-controlled volt free relay outputs (reset, fault, aux. fire and remote)
    Relay Outputs
    Reset relay is active during the panel’s reset cycle
    Relay Outputs
    Fault relay is active in any fault condition. This relay is failsafe and normally energised – if power is removed from the panel the relay will changeover to produce a fault signal
    Relay Outputs
    Aux. fire relay is active in an alarm condition provided all relevant delays have expired
    Relay Outputs
    Remote relay is active during any Alarm Condition provided all relevant delays have expired
    Outputs
    Outputs are NOT designed to switch mains voltages
    Product Information
    Product Type
    PCB mounts inside the CFP fire panel
    Products specifications
    ProtocolApollo AlarmSense
    Module TypeRelay Module
    Input Count8
    *
    *
    *